If you are viewing on a smaller screen or with screen zoom, please use the horizontal scroll bar at the bottom of this table to see all information.
ORDERING INFORMATION - D/P CONTROL
SERIES | 5900 | D/P Module | ||||
FITINGS | 1 | None, 1/8” NPT | 4 | Swagelok; 1/4” tube x 1/8" NPT (compatible with copper or poly tubing) | ||
RANGE | 0 | 0 psid to 5 psid | 2 | 0 psid to 15 psid | 4 | 0 psid to 50 psid |
1 | 0 psid to 10 psid | 3 | 0 psid to 30 psid |
If you are viewing on a smaller screen or with screen zoom, please use the horizontal scroll bar at the bottom of this table to see all information.
Output signal | 4 mAdc to 20 mAdc (milliamperes) |
Accuracy | ±0.2% F.S. (±0.10% F.S., typical) includes non-linearity, hysteresis and non-repeatability |
Repeatability | ±0.02% of calibrated span |
Temperature range | 0 °F to 180 °F/-18 °C to 82 °C (operating range) |
Compensated temperature range | 32 °F to 120 °F/ 0 °C to 54 °C |
Thermal effects (over compensated temperature range) |
Less than .007% °F (.011% °C) span shift—sensitivity Less than .007% °F (.011% °C) span shift—zero |
Power requirement* | 14 Vdc to 40 Vdc |
Power supply stability (effect on FSO) |
Less than .005% of span change in output per volt change at input terminals |
Burst pressure | 200 psi |
* Unregulated
WARNING: This product can expose you to chemicals including Lead and Nickel, which are known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov